Monday, December 12, 2011

Activity 3.1.2 Land Use and Development Regulations

1.    Identify the Building Code that applies in Noblesville by reviewing Section 154.04 Adoption of Rules by Reference in the Noblesville Code of Ordinances.
               (a)     Fire and Building Safety Standards
               (b)     Indiana Building Code
               (c)     Indiana Building Code Standards
               (d)     Indiana Handicapped Accessibility Code
2.    Visit the Indiana Association of Building Officials website at http://www.iabo.com/ and follow the link to Current Codes. On which model code is the current Indiana Building Code based?

3.    Using the International Building Code, find the Use and Occupancy classification of the proposed new Keystone Building.
 A-4 Assembly uses intended for viewing of indoor sporting events and activities with spectator seating including, but not limited to:

Arenas

Skating rinks

Swimming pools

Tennis courts

4.    Using the International Building Code, describe each of the four types of construction. Based on the existing structure, under which of these types of construction could the Keystone Building fall? See section 503.1.

602.2 Types I and II. Types I and II construction are those types of construction in which the building elements listed in Table 601 are of noncombustible materials, except as permitted in Section 603 and elsewhere in this code.

602.3 Type III. Type III construction is that type of construction in which the exterior walls are of noncombustible materials and the interior building elements are of any material permitted by this code. Fire-retardant-treated wood framing complying with Section 2303.2 shall be permitted within exterior wall assemblies of a 2-hour rating or less.

602.4 Type IV. Type IV construction (Heavy Timber, HT) is that type of construction in which the exterior walls are of noncombustible materials and the interior building elements are of solid or laminated wood without concealed spaces. The details of Type IV construction shall comply with the provisions of this section. Fire-retardant-treated wood framing complying with Section 2303.2 shall be permitted within exterior wall assemblies with a 2-hour rating or less. Minimum solid sawn nominal dimensions are required for structures built using Type IV construction (HT). For glued-laminated members the equivalent net finished width and depths corresponding to the minimum nominal width and depths of solid sawn lumber are required as specified in Table 602.4.

602.5 Type V. Type V construction is that type of construction in which the structural elements, exterior walls and interior walls are of any materials permitted by this code.

5.    Compare the allowable Building Heights and Areas (IBC 2009 Table 503) for the Keystone Library using different construction types. What is the least restrictive construction type that can be used for the Keystone Library? Is a fire-protective layer required over the structural elements? Note: The letter A indicates that the structural members are protected by a fire-rated coating or cover (sheetrock, spray on, or another approved method). The letter B indicates that the structural members are not protected by an additional fire-rated coating or cover.
Type I is the least restrictive, but isnt the most practical for a library so either Type II or IV which allow the same amount for area and floors. Yes a fire-protective layer is required over the structural elements.
6.    What materials do you propose to use for the new interior walls and floor for the Keystone Building? Justify your answer.
Walls made of laminated fire retardant wood over aluminum framing.
7.    Use the IBC to determine the Occupant Load (IBC 2009 Section 1004) for the Keystone Building assuming a second floor is added. For now, conservatively assume that the second floor is entirely stacks and that the first floor is entirely reading rooms. In addition, because there is currently no plan to include an outside stairway to the roof, assume that the occupants of the green roof must exit through the 2nd floor. The building inspector has determined, based on the planned use of the green roof as additional reading area, that the occupant load for the green roof may be based on the requirements for reading rooms.
First floor approximately 178 people.
Second floor approximately 46 people.
Green roof approximately 178 people.
8.    The occupant load is used to determine the minimum egress width for the building. Use the IBC to determine the required total egress width (IBC 2009 Section 1005) for the Keystone Building including the second floor.
For stairways 113.5 inches.
For other means of egress 89 inches.
9.    What is the minimum number of exits required for the Occupant Load (IBC 2009 Section 1021)?

10. Read IBC 2009 Section 1021.2. Is it permissible to have only a single exit from the ground floor? From the second floor? Justify your answers.

No it must have at least 2 exits per story.
The answers to the following questions should be researched in the Noblesville Code of Ordinances and the Noblesville Zoning Map.

11. In which zoning designation does the Keystone building property lie? (Refer to the Keystone Library Site Location Map to help locate the site on the zoning map.)
Planned business
12. Describe the purpose of this zoning designation. Document your answer with a section number from the code.

13. What is the minimum lot size within this designation? Does the Keystone Property meet this requirement? Document your answer with a section number of the code.

14. What is the maximum building height according to the Noblesville ordinance?

15. Read Section 159.120 of the Noblesville Code of Ordinances. Record any information that is important to the redevelopment of the Keystone building.

16. Is the Use proposed in Keystone Building Project permitted on this property?  Document your answer.

17. When developing a property, when is landscaping and screening required?